Air System Sizing Summary for 000 1PAV Esp Arquibancada
Transcrição
Air System Sizing Summary for 000 1PAV Esp Arquibancada
Air System Sizing Summary for 000 1PAV Esp Arquibancada Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ......... 000 1PAV Esp Arquibancada Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area .............................................................. 327,0 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ....................................................... 90,1 Sensible coil load .................................................. 57,1 Coil L/s at Jan 1600 ............................................. 3489 Max block L/s ...................................................... 3489 Sum of peak zone L/s .......................................... 3489 Sensible heat ratio .............................................. 0,633 m²/kW .................................................................... 3,6 W/m² .................................................................. 275,5 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1600 OA DB / WB ................................................... 35,2 / 25,6 Entering DB / WB ........................................... 25,6 / 19,3 Leaving DB / WB ........................................... 11,9 / 11,4 Coil ADP .................................................................. 10,4 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 56 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ..................................................... 3489 L/s Standard L/s ........................................................ 3452 L/s Actual max L/(s-m²) ............................................ 10,67 L/(s-m²) Fan motor BHP ........................................................ 4,89 BHP Fan motor kW .......................................................... 3,88 kW Fan static .................................................................. 600 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................ 2070 L/s L/(s-m²) ................................................................. 6,33 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 1 of 25 Air System Sizing Summary for 000 1PAV Esp Plenario Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name .................. 000 1PAV Esp Plenario Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area .............................................................. 230,0 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ....................................................... 65,5 Sensible coil load .................................................. 39,1 Coil L/s at Jan 1500 ............................................. 2253 Max block L/s ...................................................... 2253 Sum of peak zone L/s .......................................... 2253 Sensible heat ratio .............................................. 0,596 m²/kW .................................................................... 3,5 W/m² .................................................................. 285,0 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1500 OA DB / WB ................................................... 35,5 / 25,7 Entering DB / WB ........................................... 26,5 / 20,2 Leaving DB / WB ........................................... 12,0 / 11,5 Coil ADP .................................................................. 10,4 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 59 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ..................................................... 2253 L/s Standard L/s ........................................................ 2229 L/s Actual max L/(s-m²) .............................................. 9,79 L/(s-m²) Fan motor BHP ........................................................ 3,16 BHP Fan motor kW .......................................................... 2,50 kW Fan static .................................................................. 600 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................ 1725 L/s L/(s-m²) ................................................................. 7,50 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 2 of 25 Air System Sizing Summary for 1PAV Atendimento Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ......................... 1PAV Atendimento Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 25,3 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 2,7 Sensible coil load ................................................... 1,8 Coil L/s at Jan 1600 .............................................. 113 Max block L/s ....................................................... 113 Sum of peak zone L/s ........................................... 113 Sensible heat ratio .............................................. 0,665 m²/kW .................................................................... 9,3 W/m² .................................................................. 108,1 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1600 OA DB / WB ................................................... 35,2 / 25,6 Entering DB / WB ........................................... 26,5 / 19,7 Leaving DB / WB ........................................... 13,0 / 12,5 Coil ADP .................................................................. 11,5 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 54 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 113 L/s Standard L/s ......................................................... 112 L/s Actual max L/(s-m²) .............................................. 4,46 L/(s-m²) Fan motor BHP ........................................................ 0,01 BHP Fan motor kW .......................................................... 0,01 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 30 L/s L/(s-m²) ................................................................. 1,19 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 3 of 25 Air System Sizing Summary for 1PAV Cerimonial Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ............................ 1PAV Cerimonial Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area .............................................................. 110,1 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ....................................................... 20,8 Sensible coil load .................................................. 14,2 Coil L/s at Dec 1400 ............................................. 916 Max block L/s ....................................................... 916 Sum of peak zone L/s ........................................... 916 Sensible heat ratio .............................................. 0,684 m²/kW .................................................................... 5,3 W/m² .................................................................. 189,1 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Dec 1400 OA DB / WB ................................................... 34,6 / 25,6 Entering DB / WB ........................................... 25,8 / 19,0 Leaving DB / WB ........................................... 12,8 / 12,2 Coil ADP .................................................................. 11,3 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 52 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 916 L/s Standard L/s ......................................................... 907 L/s Actual max L/(s-m²) .............................................. 8,32 L/(s-m²) Fan motor BHP ........................................................ 0,11 BHP Fan motor kW .......................................................... 0,08 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................. 203 L/s L/(s-m²) ................................................................. 1,84 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 4 of 25 Air System Sizing Summary for 1PAV ChefeDepartamento1 Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ........... 1PAV ChefeDepartamento1 Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 17,3 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 3,8 Sensible coil load ................................................... 3,0 Coil L/s at Feb 1700 ............................................. 223 Max block L/s ....................................................... 223 Sum of peak zone L/s ........................................... 223 Sensible heat ratio .............................................. 0,806 m²/kW .................................................................... 4,6 W/m² .................................................................. 217,2 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Feb 1700 OA DB / WB ................................................... 34,5 / 25,5 Entering DB / WB ........................................... 24,5 / 17,7 Leaving DB / WB ........................................... 13,2 / 12,5 Coil ADP .................................................................. 11,9 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 51 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 223 L/s Standard L/s ......................................................... 221 L/s Actual max L/(s-m²) ............................................ 12,89 L/(s-m²) Fan motor BHP ........................................................ 0,03 BHP Fan motor kW .......................................................... 0,02 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 23 L/s L/(s-m²) ................................................................. 1,30 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 5 of 25 Air System Sizing Summary for 1PAV ChefeDepartamento2 Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ........... 1PAV ChefeDepartamento2 Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 17,9 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 4,5 Sensible coil load ................................................... 3,8 Coil L/s at Feb 1600 ............................................. 282 Max block L/s ....................................................... 282 Sum of peak zone L/s ........................................... 282 Sensible heat ratio .............................................. 0,836 m²/kW .................................................................... 3,9 W/m² .................................................................. 253,2 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Feb 1600 OA DB / WB ................................................... 35,2 / 25,6 Entering DB / WB ........................................... 24,2 / 17,3 Leaving DB / WB ........................................... 12,9 / 12,3 Coil ADP .................................................................. 11,7 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 50 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 282 L/s Standard L/s ......................................................... 279 L/s Actual max L/(s-m²) ............................................ 15,76 L/(s-m²) Fan motor BHP ........................................................ 0,03 BHP Fan motor kW .......................................................... 0,03 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 23 L/s L/(s-m²) ................................................................. 1,26 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 6 of 25 Air System Sizing Summary for 1PAV Circulacao4a Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ........................ 1PAV Circulacao4a Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area .............................................................. 194,0 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ....................................................... 21,3 Sensible coil load .................................................. 15,5 Coil L/s at Feb 1700 ............................................ 1091 Max block L/s ...................................................... 1091 Sum of peak zone L/s .......................................... 1091 Sensible heat ratio .............................................. 0,729 m²/kW .................................................................... 9,1 W/m² .................................................................. 109,6 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Feb 1700 OA DB / WB ................................................... 34,5 / 25,5 Entering DB / WB ........................................... 24,8 / 18,3 Leaving DB / WB ........................................... 12,9 / 12,3 Coil ADP .................................................................. 11,6 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 53 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ..................................................... 1091 L/s Standard L/s ........................................................ 1080 L/s Actual max L/(s-m²) .............................................. 5,62 L/(s-m²) Fan motor BHP ........................................................ 0,13 BHP Fan motor kW .......................................................... 0,10 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................. 147 L/s L/(s-m²) ................................................................. 0,76 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 3,80 L/s/person Page 7 of 25 Air System Sizing Summary for 1PAV Circulacao5 Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name .......................... 1PAV Circulacao5 Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 12,8 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 1,2 Sensible coil load ................................................... 0,8 Coil L/s at Dec 1400 ............................................... 55 Max block L/s ......................................................... 55 Sum of peak zone L/s ............................................. 55 Sensible heat ratio .............................................. 0,683 m²/kW ................................................................... 10,6 W/m² .................................................................... 94,3 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Dec 1400 OA DB / WB ................................................... 34,6 / 25,6 Entering DB / WB ........................................... 25,3 / 18,8 Leaving DB / WB ........................................... 12,7 / 12,2 Coil ADP .................................................................. 11,3 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 54 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ........................................................ 55 L/s Standard L/s ........................................................... 54 L/s Actual max L/(s-m²) .............................................. 4,28 L/(s-m²) Fan motor BHP ........................................................ 0,01 BHP Fan motor kW .......................................................... 0,01 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 10 L/s L/(s-m²) ................................................................. 0,76 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 3,80 L/s/person Page 8 of 25 Air System Sizing Summary for 1PAV Circulacao6 Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name .......................... 1PAV Circulacao6 Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 12,8 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 1,5 Sensible coil load ................................................... 1,0 Coil L/s at Jan 1400 ................................................ 55 Max block L/s ......................................................... 55 Sum of peak zone L/s ............................................. 55 Sensible heat ratio .............................................. 0,626 m²/kW .................................................................... 8,3 W/m² .................................................................. 120,4 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1400 OA DB / WB ................................................... 35,2 / 25,6 Entering DB / WB ........................................... 27,5 / 20,4 Leaving DB / WB ........................................... 12,7 / 12,2 Coil ADP .................................................................. 11,1 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 54 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ........................................................ 55 L/s Standard L/s ........................................................... 54 L/s Actual max L/(s-m²) .............................................. 4,28 L/(s-m²) Fan motor BHP ........................................................ 0,01 BHP Fan motor kW .......................................................... 0,01 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 19 L/s L/(s-m²) ................................................................. 1,50 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 9 of 25 Air System Sizing Summary for 1PAV Circulacao7 Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name .......................... 1PAV Circulacao7 Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area .............................................................. 118,0 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ....................................................... 17,3 Sensible coil load .................................................. 13,7 Coil L/s at Dec 1500 ............................................ 1029 Max block L/s ...................................................... 1029 Sum of peak zone L/s .......................................... 1029 Sensible heat ratio .............................................. 0,792 m²/kW .................................................................... 6,8 W/m² .................................................................. 146,7 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Dec 1500 OA DB / WB ................................................... 34,9 / 25,7 Entering DB / WB ........................................... 24,3 / 17,8 Leaving DB / WB ........................................... 13,2 / 12,6 Coil ADP .................................................................. 11,9 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 52 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ..................................................... 1029 L/s Standard L/s ........................................................ 1018 L/s Actual max L/(s-m²) .............................................. 8,72 L/(s-m²) Fan motor BHP ........................................................ 0,12 BHP Fan motor kW .......................................................... 0,10 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 90 L/s L/(s-m²) ................................................................. 0,76 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 3,80 L/s/person Page 10 of 25 Air System Sizing Summary for 1PAV Circulacao8 Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name .......................... 1PAV Circulacao8 Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area .............................................................. 254,0 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ....................................................... 33,1 Sensible coil load .................................................. 25,5 Coil L/s at Jan 1600 ............................................. 1858 Max block L/s ...................................................... 1858 Sum of peak zone L/s .......................................... 1858 Sensible heat ratio .............................................. 0,770 m²/kW .................................................................... 7,7 W/m² .................................................................. 130,3 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1600 OA DB / WB ................................................... 35,2 / 25,6 Entering DB / WB ........................................... 24,6 / 18,0 Leaving DB / WB ........................................... 13,1 / 12,5 Coil ADP .................................................................. 11,8 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 53 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ..................................................... 1858 L/s Standard L/s ........................................................ 1839 L/s Actual max L/(s-m²) .............................................. 7,31 L/(s-m²) Fan motor BHP ........................................................ 0,22 BHP Fan motor kW .......................................................... 0,17 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................. 193 L/s L/(s-m²) ................................................................. 0,76 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 3,80 L/s/person Page 11 of 25 Air System Sizing Summary for 1PÀV Copa Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ..................................... 1PÀV Copa Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 19,5 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 6,6 Sensible coil load ................................................... 5,7 Coil L/s at Dec 1500 ............................................. 430 Max block L/s ....................................................... 430 Sum of peak zone L/s ........................................... 430 Sensible heat ratio .............................................. 0,855 m²/kW .................................................................... 3,0 W/m² .................................................................. 338,9 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Dec 1500 OA DB / WB ................................................... 34,9 / 25,7 Entering DB / WB ........................................... 24,1 / 17,3 Leaving DB / WB ........................................... 13,1 / 12,5 Coil ADP .................................................................. 11,9 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 50 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 430 L/s Standard L/s ......................................................... 425 L/s Actual max L/(s-m²) ............................................ 22,04 L/(s-m²) Fan motor BHP ........................................................ 0,05 BHP Fan motor kW .......................................................... 0,04 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 30 L/s L/(s-m²) ................................................................. 1,54 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 12 of 25 Air System Sizing Summary for 1PAV DivisaoComunicacaoEx Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ...... 1PAV DivisaoComunicacaoEx Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 52,3 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 5,6 Sensible coil load ................................................... 4,9 Coil L/s at Jan 1600 .............................................. 372 Max block L/s ....................................................... 372 Sum of peak zone L/s ........................................... 372 Sensible heat ratio .............................................. 0,867 m²/kW .................................................................... 9,3 W/m² .................................................................. 107,3 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1600 OA DB / WB ................................................... 35,2 / 25,6 Entering DB / WB ........................................... 24,0 / 17,1 Leaving DB / WB ........................................... 13,0 / 12,4 Coil ADP .................................................................. 11,8 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 50 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 372 L/s Standard L/s ......................................................... 368 L/s Actual max L/(s-m²) .............................................. 7,11 L/(s-m²) Fan motor BHP ........................................................ 0,04 BHP Fan motor kW .......................................................... 0,03 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 23 L/s L/(s-m²) ................................................................. 0,43 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 13 of 25 Air System Sizing Summary for 1PAV Plenario_Arquibancada Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ....... 1PAV Plenario_Arquibancada Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area .............................................................. 557,0 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ..................................................... 156,7 Sensible coil load .................................................. 96,6 Coil L/s at Jan 1600 ............................................. 5741 Max block L/s ...................................................... 5741 Sum of peak zone L/s .......................................... 5741 Sensible heat ratio .............................................. 0,617 m²/kW .................................................................... 3,6 W/m² .................................................................. 281,3 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1600 OA DB / WB ................................................... 35,2 / 25,6 Entering DB / WB ........................................... 25,8 / 19,5 Leaving DB / WB ........................................... 11,7 / 11,3 Coil ADP .................................................................. 10,2 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 57 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ..................................................... 5741 L/s Standard L/s ........................................................ 5681 L/s Actual max L/(s-m²) ............................................ 10,31 L/(s-m²) Fan motor BHP ........................................................ 8,04 BHP Fan motor kW .......................................................... 6,38 kW Fan static .................................................................. 600 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................ 3795 L/s L/(s-m²) ................................................................. 6,81 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 14 of 25 Air System Sizing Summary for 1PAV Preparo Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ................................. 1PAV Preparo Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 16,0 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 8,3 Sensible coil load ................................................... 7,7 Coil L/s at Dec 1700 ............................................. 884 Max block L/s ....................................................... 884 Sum of peak zone L/s ........................................... 884 Sensible heat ratio .............................................. 0,926 m²/kW .................................................................... 1,9 W/m² .................................................................. 520,7 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Dec 1700 OA DB / WB ................................................... 33,9 / 25,4 Entering DB / WB ........................................... 23,6 / 18,5 Leaving DB / WB ........................................... 16,3 / 15,8 Coil ADP .................................................................. 15,4 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 62 Design supply temp. ................................................ 16,0 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 884 L/s Standard L/s ......................................................... 874 L/s Actual max L/(s-m²) ............................................ 55,22 L/(s-m²) Fan motor BHP ........................................................ 0,10 BHP Fan motor kW .......................................................... 0,08 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 23 L/s L/(s-m²) ................................................................. 1,43 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 3,80 L/s/person Page 15 of 25 Air System Sizing Summary for 1PAV Public Anais Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ......................... 1PAV Public Anais Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 59,8 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ....................................................... 10,0 Sensible coil load ................................................... 8,1 Coil L/s at Mar 1600 ............................................. 610 Max block L/s ....................................................... 610 Sum of peak zone L/s ........................................... 610 Sensible heat ratio .............................................. 0,814 m²/kW .................................................................... 6,0 W/m² .................................................................. 166,8 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Mar 1600 OA DB / WB ................................................... 34,1 / 25,1 Entering DB / WB ........................................... 24,4 / 17,7 Leaving DB / WB ........................................... 13,3 / 12,6 Coil ADP .................................................................. 12,0 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 51 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 610 L/s Standard L/s ......................................................... 604 L/s Actual max L/(s-m²) ............................................ 10,20 L/(s-m²) Fan motor BHP ........................................................ 0,07 BHP Fan motor kW .......................................................... 0,06 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 60 L/s L/(s-m²) ................................................................. 1,00 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 16 of 25 Air System Sizing Summary for 1PAV Recepcao1 Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ............................ 1PAV Recepcao1 Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 13,9 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 3,8 Sensible coil load ................................................... 2,1 Coil L/s at Jan 1400 .............................................. 102 Max block L/s ....................................................... 102 Sum of peak zone L/s ........................................... 102 Sensible heat ratio .............................................. 0,560 m²/kW .................................................................... 3,7 W/m² .................................................................. 270,6 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1400 OA DB / WB ................................................... 35,2 / 25,6 Entering DB / WB ........................................... 30,4 / 22,8 Leaving DB / WB ........................................... 13,0 / 12,5 Coil ADP .................................................................. 11,1 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 60 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 102 L/s Standard L/s ......................................................... 101 L/s Actual max L/(s-m²) .............................................. 7,32 L/(s-m²) Fan motor BHP ........................................................ 0,01 BHP Fan motor kW .......................................................... 0,01 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 60 L/s L/(s-m²) ................................................................. 4,32 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 17 of 25 Air System Sizing Summary for 1PAV Recepcao2 Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ............................ 1PAV Recepcao2 Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 15,6 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 3,9 Sensible coil load ................................................... 3,4 Coil L/s at Apr 1700 .............................................. 270 Max block L/s ....................................................... 270 Sum of peak zone L/s ........................................... 270 Sensible heat ratio .............................................. 0,888 m²/kW .................................................................... 4,0 W/m² .................................................................. 247,9 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Apr 1700 OA DB / WB ................................................... 32,2 / 24,3 Entering DB / WB ........................................... 23,9 / 17,0 Leaving DB / WB ........................................... 13,2 / 12,6 Coil ADP .................................................................. 12,0 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 50 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 270 L/s Standard L/s ......................................................... 268 L/s Actual max L/(s-m²) ............................................ 17,33 L/(s-m²) Fan motor BHP ........................................................ 0,03 BHP Fan motor kW .......................................................... 0,03 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 15 L/s L/(s-m²) ................................................................. 0,96 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 18 of 25 Air System Sizing Summary for 1PAV RecepcaoCerimonial Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ........... 1PAV RecepcaoCerimonial Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 15,6 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 3,9 Sensible coil load ................................................... 3,4 Coil L/s at Apr 1700 .............................................. 270 Max block L/s ....................................................... 270 Sum of peak zone L/s ........................................... 270 Sensible heat ratio .............................................. 0,888 m²/kW .................................................................... 4,0 W/m² .................................................................. 247,9 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Apr 1700 OA DB / WB ................................................... 32,2 / 24,3 Entering DB / WB ........................................... 23,9 / 17,0 Leaving DB / WB ........................................... 13,2 / 12,6 Coil ADP .................................................................. 12,0 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 50 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 270 L/s Standard L/s ......................................................... 268 L/s Actual max L/(s-m²) ............................................ 17,33 L/(s-m²) Fan motor BHP ........................................................ 0,03 BHP Fan motor kW .......................................................... 0,03 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 15 L/s L/(s-m²) ................................................................. 0,96 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 19 of 25 Air System Sizing Summary for 1PAV Restaurante Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name .......................... 1PAV Restaurante Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area .............................................................. 392,4 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ....................................................... 85,6 Sensible coil load .................................................. 57,4 Coil L/s at Dec 1600 ............................................ 3698 Max block L/s ...................................................... 3698 Sum of peak zone L/s .......................................... 3698 Sensible heat ratio .............................................. 0,671 m²/kW .................................................................... 4,6 W/m² .................................................................. 218,2 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Dec 1600 OA DB / WB ................................................... 34,6 / 25,6 Entering DB / WB ........................................... 26,1 / 19,4 Leaving DB / WB ........................................... 13,1 / 12,5 Coil ADP .................................................................. 11,6 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 54 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ..................................................... 3698 L/s Standard L/s ........................................................ 3660 L/s Actual max L/(s-m²) .............................................. 9,42 L/(s-m²) Fan motor BHP ........................................................ 0,43 BHP Fan motor kW .......................................................... 0,34 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................. 897 L/s L/(s-m²) ................................................................. 2,29 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 3,80 L/s/person Page 20 of 25 Air System Sizing Summary for 1PAV Sala Tecnica Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ......................... 1PAV Sala Tecnica Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 12,2 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 9,5 Sensible coil load ................................................... 6,9 Coil L/s at Dec 1400 ............................................. 551 Max block L/s ....................................................... 551 Sum of peak zone L/s ........................................... 551 Sensible heat ratio .............................................. 0,727 m²/kW .................................................................... 1,3 W/m² .................................................................. 780,8 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Dec 1400 OA DB / WB ................................................... 34,6 / 25,6 Entering DB / WB ........................................... 23,6 / 17,8 Leaving DB / WB ........................................... 13,0 / 12,5 Coil ADP .................................................................. 11,9 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 58 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 551 L/s Standard L/s ......................................................... 545 L/s Actual max L/(s-m²) ............................................ 45,15 L/(s-m²) Fan motor BHP ........................................................ 0,06 BHP Fan motor kW .......................................................... 0,05 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 14 L/s L/(s-m²) ................................................................. 1,12 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 6,85 L/s/person Page 21 of 25 Air System Sizing Summary for 1PAV SecretarioDepart Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name .................. 1PAV SecretarioDepart Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 25,9 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 4,3 Sensible coil load ................................................... 2,7 Coil L/s at Jan 1500 .............................................. 156 Max block L/s ....................................................... 156 Sum of peak zone L/s ........................................... 156 Sensible heat ratio .............................................. 0,621 m²/kW .................................................................... 6,0 W/m² .................................................................. 166,3 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1500 OA DB / WB ................................................... 35,5 / 25,7 Entering DB / WB ........................................... 27,4 / 20,6 Leaving DB / WB ........................................... 13,1 / 12,5 Coil ADP .................................................................. 11,5 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 56 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 156 L/s Standard L/s ......................................................... 154 L/s Actual max L/(s-m²) .............................................. 6,02 L/(s-m²) Fan motor BHP ........................................................ 0,02 BHP Fan motor kW .......................................................... 0,01 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 53 L/s L/(s-m²) ................................................................. 2,03 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 22 of 25 Air System Sizing Summary for 1PAV SlAutomacao Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ........................ 1PAV SlAutomacao Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 22,9 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 7,4 Sensible coil load ................................................... 6,8 Coil L/s at Dec 1500 ............................................. 547 Max block L/s ....................................................... 547 Sum of peak zone L/s ........................................... 547 Sensible heat ratio .............................................. 0,927 m²/kW .................................................................... 3,1 W/m² .................................................................. 322,0 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Dec 1500 OA DB / WB ................................................... 34,9 / 25,7 Entering DB / WB ........................................... 24,0 / 17,0 Leaving DB / WB ........................................... 13,5 / 12,8 Coil ADP .................................................................. 12,3 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 50 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 0 of 1 Max zone temperature deviation ................................ 0,2 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 547 L/s Standard L/s ......................................................... 541 L/s Actual max L/(s-m²) ............................................ 23,87 L/(s-m²) Fan motor BHP ........................................................ 0,06 BHP Fan motor kW .......................................................... 0,05 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 12 L/s L/(s-m²) ................................................................. 0,54 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 3,80 L/s/person Page 23 of 25 Air System Sizing Summary for 1PAV SuperintendenciaRH Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ............ 1PAV SuperintendenciaRH Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area .............................................................. 123,3 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ....................................................... 20,7 Sensible coil load .................................................. 15,2 Coil L/s at Jan 1600 ............................................. 1037 Max block L/s ...................................................... 1037 Sum of peak zone L/s .......................................... 1037 Sensible heat ratio .............................................. 0,734 m²/kW .................................................................... 6,0 W/m² .................................................................. 167,9 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Jan 1600 OA DB / WB ................................................... 35,2 / 25,6 Entering DB / WB ........................................... 25,3 / 18,5 Leaving DB / WB ........................................... 13,0 / 12,4 Coil ADP .................................................................. 11,7 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 52 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ..................................................... 1037 L/s Standard L/s ........................................................ 1026 L/s Actual max L/(s-m²) .............................................. 8,41 L/(s-m²) Fan motor BHP ........................................................ 0,12 BHP Fan motor kW .......................................................... 0,10 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................. 173 L/s L/(s-m²) ................................................................. 1,40 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 7,50 L/s/person Page 24 of 25 Air System Sizing Summary for 1PAV SuperintendenteRH Project Name: Assembleia_Legislativa_RO_01PV_R3_22jun15 Prepared by: Termacon Projetos e Consultoria Ltda 11/04/2015 01:39 Air System Information Air System Name ............. 1PAV SuperintendenteRH Equipment Class ....................................... SPLT AHU Air System Type ............................................. SZCAV Number of zones .......................................................... 1 Floor Area ................................................................ 25,7 m² Location ........................................... Porto Velho, Brazil Sizing Calculation Information Zone and Space Sizing Method: Zone L/s ......................... Sum of space airflow rates Space L/s ..................... Individual peak space loads Calculation Months ....................................... Jan to Dec Sizing Data ................................................... Calculated Central Cooling Coil Sizing Data Total coil load ........................................................ 5,7 Sensible coil load ................................................... 4,6 Coil L/s at Dec 1600 ............................................. 349 Max block L/s ....................................................... 349 Sum of peak zone L/s ........................................... 349 Sensible heat ratio .............................................. 0,806 m²/kW .................................................................... 4,5 W/m² .................................................................. 223,1 Water flow @ 5,6 °K rise ....................................... N/A kW kW L/s L/s L/s Load occurs at ................................................. Dec 1600 OA DB / WB ................................................... 34,6 / 25,6 Entering DB / WB ........................................... 24,2 / 17,6 Leaving DB / WB ........................................... 13,2 / 12,6 Coil ADP .................................................................. 12,0 Bypass Factor ........................................................ 0,100 Resulting RH .............................................................. 52 Design supply temp. ................................................ 12,8 Zone T-stat Check ................................................. 1 of 1 Max zone temperature deviation ................................ 0,0 °C °C °C °C % °C OK °K Supply Fan Sizing Data Actual max L/s ...................................................... 349 L/s Standard L/s ......................................................... 346 L/s Actual max L/(s-m²) ............................................ 13,60 L/(s-m²) Fan motor BHP ........................................................ 0,04 BHP Fan motor kW .......................................................... 0,03 kW Fan static .................................................................... 50 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................... 27 L/s L/(s-m²) ................................................................. 1,04 L/(s-m²) Hourly Analysis Program v4.70 L/s/person ................................................................ 3,80 L/s/person Page 25 of 25